Battery Monitoring Systems
Transducers
Protective Relays
Digital Meters
Analog Meters
Catalog Order
Product Bulletins
Software Download
About Us
Contact Us
Employment Opportunities
Return to the Home Page.
Trade Shows
Texas A&M
Mar 31-Apr 3 2014
College Station, Tx.

IEEE/PES T&D
Apr 14-17 2014
Chicago, Il

(more info)

Georgia Tech
Apr 28-May 3 2014
Atlanta, GA

Battcon
May 5-7 2014
Boca Raton, Fl

(more info)

NEPPA Annual
Aug 24-27 2014
Fallmouth, Ma

(more info)

Western Protective Relay
Oct 14-16 2014
Spokane, Wa

(more info)

MIPSYCON
Nov 4-6 2014
Minneapolis, Mn





Arga Controls Unit of ELECTROSWITCH CORP.
      Measurement and Control Instrumentation - Commercial · Industrial · Utility · Government
       9654 Hermosa Ave • Rancho Cucamonga • CA 91730 • Tel: 626-799-3314 • FAX: 626-799-9407 • E-mail: info@argacontrols.com

Battery Monitor Specifications

Battery Monitor: Part No.25-469

SPECIFICATIONS

1. Battery Input: 90 to 180 VDC, 3VA- For 125 V Battery*

2. Ground Resistors: 30K ±1% from each bus to ground

3. Voltage Indication: 0 to ±199.9 VDC in 0.6" bright red LED digit and decimal point. Accuracy is ±0.2 VDC

4. Ranges:

A. + Bus to Ground (+to GND)
B. -Bus to Ground (-to GND)
C. Ground Fault Voltage (Fault)
D. Battery Voltage (BAT)
5. Scanning: Automatically scans each range. Each reading is 3 seconds. Scanning stops on indicated value when scanlmanual is pushed. Scan resumes on next reading when pushed again. LED lights indicate range being shown. Scanning stops and displays alarm values.

6. Alarms: (Not Scanned)

A. "+Fault" relay energizes and latches when the + fault voltage exceeds the + set value for the time setting. The "alarm" LED lights. Set range is 13.0 to - 100.0V.
B. "-Fault" relay energizes and latches when the -fault voltage exceeds the - set value for the time setting. The "alarm" LED lights. Set range is -13.0 to - 100.0V.

C. "Hi Battery" relay energizes and latches when the battery voltage exceeds the "Hi" set value for the time setting. The "alarm" LED lights. Set range is 125.0 to 150.0V.

D. "Lo Battery" relay de-energizes and latches when the battery voltage is below the "Lo" set value for the time setting. The "alarm" LED lights. Set range is 100.0 to 125.0V.

7. Time Delay: Can be set from 5 to 60 seconds.

8. Reset: Panel push button or remote contact closure will reset an alarm provided the cause is removed.

9. Contact Rating: 2A at 120 VAC or 28 VDC.

10. Limit Setting: Display of limit setting by pushing the "limit" on front panel when range light is on. Limits and time delay are set by removing the front bezel (4 screws). This can safely be done with power on.

11: Output Options

A. 0 to 1 mADC (isolated) into 0 to 10K load for 90 to 180 VDC input. Accuracy is :±0.1% of FS. PIN is 25-469-101.

B. 4 to 20 mADC (isolated) into 0 to 500 OHM load for 90 to 180 VDC input. Accuracy is :to. 1 % of FS. PIN is 25-469-1420

C. Digital: RS232/485 with DNP3.0 or Modbus, PIN is 25-469-J3.0 .

*Additional Voltages P/N: 25-471 = 48 V Battery   P/N: 25-472 = 250 V Battery.
Other voltages available - consult factory.

Optional Fault Indicator

Fault Indicator SPECIFICATIONS

1. Operation: Produces current pulses between the transmitter and the ground fault. A pulse receiver can trace the line with these pulses to the ground. Circuit breaker in this line can be identified and opened to clean the ground from the system.

2. Option Availability: on the 25-469, 25-471, 25-472, specify suffix BB in addition to others.

3. Features:

A. On/off switch on front panel
B. Automatic Selection of grounded line.
C. Does not interfere with sensitive electronic equipment, radio, etc.
4. Receiver: Arga P/N 200A
A. Hand held
B. Does not contact circuitry
C. LED & sound indications
5. Sensitivity: Up to 100OHMS ground resistance.

Click Here to print specification page Print this Arga Controls Spec Page.
Get Adobe Acrobat Reader

 

 

9654 Hermosa Ave • Rancho cucamonga • CA 91730 • Tel: 626-799-3314 • FAX: 626-799-9407 • E-mail: info@argacontrols.com